It’s the first question almost every Lagos buyer asks: will solar actually run my air conditioners? The short answer is yes, whether they are inverter ACs or standard ones. What changes is how big the system needs to be, and that comes down to which ACs you have and how many you want running at night.
Inverter or standard AC: both run on solar
You don’t need to replace your air conditioners to go solar. Most Lagos homes have a mix, and a correctly sized system runs either kind. The difference is how much power each one asks for.
Inverter (variable-speed) ACs slow down once the room is cool instead of switching on and off, and they start gently. A 1.5HP inverter AC draws about 1.2 kW while it pulls the room down, then settles to roughly 0.5–0.9 kW.
Standard (non-inverter) ACs run at full power whenever the compressor is on, about 1.1–1.4 kW for a 1.5HP unit, and draw three to five times that for a second as the compressor starts. A hybrid inverter is built to ride through short surges like that, so a standard AC runs on solar without trouble. We just size for it:
- Start-up headroom. We leave room on the inverter for the surge, so a compressor starting while the fridge and pump are running doesn’t trip it. A soft-starter fitted to the AC cuts the surge sharply and costs far less than a bigger inverter.
- A bit more battery for the same night. Over a night a standard AC typically uses 30–50% more electricity than an inverter one, so either the battery is larger or the AC runs for fewer hours on it.
- Upgrade when it suits you. If an AC needs replacing anyway, an inverter model lets the same system cool for longer. There is no need to replace working units before you go solar.
You don’t need to know any of this to ask for a quote. Tell us your monthly power bill and we size the system from it, then check the ACs already on your walls during the site survey.
How many ACs can each system run?
What each Solepower home system carries, from the package specifications. The figures are for inverter ACs; with standard units, expect fewer hours on battery at night. The site survey sizes your system from your full load.
| System | Air conditioners | Overnight on battery |
|---|---|---|
| 6.2 kVA · 10 kWh | 1 unit (1.5HP) | 6 hours at 1.5 kW |
| 6 kVA · 15 kWh | 1 unit (1.5HP) continuously, or 2 units alternating | 9 hours at 1.5 kW |
| 10 kVA · 30 kWh | 2 units (1.5HP) together | 11 hours at 2.5 kW |
| 11 kVA · 30 kWh | 2 units (1.5HP) together, a third in sunshine hours | 11 hours at 2.5 kW |
| 12 kVA · 30 kWh | 2–3 units (1.5HP) together | 9 hours at 3 kW |
| 18 kVA · 30 kWh | 4 units (1.5HP) together in the day, 2 at night | 7 hours at 4 kW |
You can see the complete range on the Packages page, and how sizing works in our Lagos sizing guide.
Running ACs at night is really about the battery
Through the day, your ACs run largely straight off the panels. Overnight, they run off the battery. If you want bedrooms cooled all night, the battery (kWh) is the number to size up. For most homes, overnight cooling is the single biggest factor in how large the battery needs to be.
How a system performs
A typical day, and what it can carry
4–5 bedroom home or office with 10–15 staff in Lagos, where 2–3 ACs run all day
- Straight from the panels: 14 kWh
- From the battery: 18 kWh
- Essentials only: Fridge, lights, fans, TV, Wi-Fi (about 1 kW)27 hrs
- 6 kW: 2 ACs, fridge, workstations and lights4.5 hrs
- 9 kW: 2–3 ACs and the full home or office load3 hrs
What it runs
- ACs: 2–3 units (1.5HP) together
- Fridges: 2 fridges, or 1 fridge and 1 large chest freezer, around the clock
- Water pump: 1HP submersible borehole pump: yes
- Washing: Yes, 1–2 loads a day
Show the hourly numbers
| Hour | Solar (kW) | In use (kW) | Battery |
|---|---|---|---|
| 12am | 0 | 1.1 | 55% |
| 1am | 0 | 0.9 | 52% |
| 2am | 0 | 0.9 | 48% |
| 3am | 0 | 0.9 | 45% |
| 4am | 0 | 0.9 | 41% |
| 5am | 0 | 1.1 | 37% |
| 6am | 0 | 1.3 | 33% |
| 7am | 1.5 | 1.4 | 33% |
| 8am | 2.8 | 1.2 | 39% |
| 9am | 4 | 1.1 | 49% |
| 10am | 4.9 | 1.1 | 62% |
| 11am | 5.5 | 1.2 | 77% |
| 12pm | 5.6 | 1.3 | 93% |
| 1pm | 5.5 | 1.3 | 100% |
| 2pm | 4.9 | 1.3 | 100% |
| 3pm | 4 | 1.3 | 100% |
| 4pm | 2.8 | 1.4 | 100% |
| 5pm | 1.5 | 1.7 | 99% |
| 6pm | 0 | 1.9 | 92% |
| 7pm | 0 | 2 | 85% |
| 8pm | 0 | 2 | 77% |
| 9pm | 0 | 1.9 | 70% |
| 10pm | 0 | 1.7 | 64% |
| 11pm | 0 | 1.3 | 59% |
Illustrative, not a measurement. Solar output is this package's rated daily generation spread over a clear-day curve; use follows a typical home (evening peak) pattern at the daily use the package is designed for. Cloudy and harmattan days produce less. Backup hours at the two higher loads are the figures on the package page; the essentials row assumes about 1 kW.
Simple habits that stretch the system
- Set ACs to 24–25°C rather than 18°C. The compressor works far less.
- When an AC is due for replacement, choose an inverter model. It lets the same battery cool for longer.
- Cool the rooms you're actually using, not the whole house.
- Run heavy daytime loads (laundry, water pumps, ironing) while the sun is up and the panels are producing.
- Keep filters clean; a clogged AC draws more power for less cooling.